• Top
  • +86 18923842907
  • QR code
  • 1、Basic Infomation

    ◆ Place of Origin: CN

    ◆ Brand Name: Eltek

    ◆ Certification: CE.UL

    ◆ Model Number: CTE30834R1.4000

     

    2、Payment & Shipping Terms

    ◆ Delivery Time: 8-10 weeks

    ◆ Payment Terms: L/C, T/T

    ◆ Supply Ability: 400 sets /month

     

    3、Product Description

     

    Eltek Rectiverter Outdoor system 6 kVA AC up to 21KW 48Vdc Output AC DC rectiverter outdoor cabinet (CTE30834R1.4000 )
     

    The Rectiverter outdoor system combines both AC and DC feed into one common unit. Simultaneously it provides AC backup power for 230 Vac loads, and 48 Vdc power for DC loads and battery charging.

     

    With our Type 3 cabinet platform it’s designed for a protection class of IP55. The total DC output can be configured up to 21kW DC load where the limitation for AC load is set to max 6kVA.

     

    Key features

    ◆ l 230 Vac single phase input

    ◆ l 400 Vac three phase input

    ◆ l 48 Vdc input/output

    ◆ l Single phase output

    ◆ l Max 6kVA AC output

    ◆ l Max 21kW DC output

    ◆ l 1 pole AC distribution option

    ◆ l 2 pole AC distribution option

    ◆ l -48 Vdc distribution option

    ◆ l Built in transfer technology

    ◆ l 150% overload capability, 15s

    ◆ l 600% quick trip current, 20ms

    ◆ l Hot pluggable

    ◆ l Smartpack2 controller

    ◆ l Smartpack S controller

     
    Parameters :

     

     
    Models / ordering information 6kVA+12,8 kW DC 6kVA+16,8kW DC 6kVA+ 16,0 kW DC 6kVA+21,0kW DC
    Part number CTEJ0834.4000 CTEJ0834.4001 CTE20834R1.4000 CTE30834R1.4000
    AC OUTPUT DATA
    Voltage (default) / (adjustable range) 230 VAC / 200 - 240 VAC
    Frequency (default inverter mode) 50 Hz (adaptive)
    Frequency (set-able inverter mode) 50Hz, 60Hz or last synced 50/60Hz (adaptive)
    Power maximum (continuous / overload (<15s) ) 4800 W (6000 VA) / 8000 VA
    Current maximum (continuous / overload (<15s) ) 26ARMS / 34,8ARMS
    Current (maximum) Quick trip (20ms) 120A (6 x nominal)

    Hold up (Voltage dips) (before switching to > 5 ms @ 4800W load

    battery)

    THD < 1.5 % at resistive load
    Output features Fuse in L and N, Hot pluggable
    DC OUTPUT DATA
    Voltage (default) / (adjustable range) 53.5 VDC / 43 - 58 VDC
    Power (maximum @nominal input) 12,8 kW 1) 16,8 kW 1) 16,0 kW 1) 21,0 kW 1)
    Current (maximum @VOUT ≤ 48 VDC) 267 A 1) 350 A 1) 333 A 1) 437 A 1)
    Hold up time, maximum output power >10ms; VOUT > 41 VDC
    Output features Short circuit proof, Over voltage Shutdown
    INPUT DATA
    AC Mains Input Voltage (3 phase Y) 400 VAC
    Surge Protection OVP Class 2
    AC Current/Phase(at nominal output voltage) (depending on type) 28-58 ARMS 3)
    Frequency (default: sync range) 47-53 Hz
    Frequency (set-able: sync range) 47-53 Hz, 57-63 Hz or both (adaptive)
    Power Factor / THD > 0.99 at 50% load or more / < 3.5%

    DC Voltage nominal / extended range (no 45 - 58 V / 40 - 45 V

    overload)2) DC DC

    DC Current (maximum) 128 A / 180A during overload (15s)

    Fuse in L and N, Hot pluggable, Varistor, Hot pluggable

    Input features AC input individual screw terminals 10 mm2 for L1, L2, L3, N & PE Battery breaker (plug-in type), LVBD default

    LOAD DISTRIBUTION 6kVA+12,8kW DC 6kVA+16,8kW DC 6kVA+16,0 kW DC 6kVA+21,0 kW DC
    LVLD 150 A -
    1 pole AC distribution (L connection on MCB) 2*6A, 2*10A C
    -48 VDC distribution ( priority load ) 2*10A,2*16A,2*32A,2*63A 2*10A, 2*32A,2*63A 2*10A,2*16A,2*32A,2*63A 2*10A,2*16A,3*32A,3*63A
    -48 VDC distribution (no priority load) 2*10A, 2*32A, 2*63A -
    Battery breaker 2*100 A, D (plug-in) 2*200 A, D (plug-in) 2*200 A, D (plug-in) 2*250 A, D (plug-in)
    OTHER SPECIFICATION
    Control and monitoring (see Smartpack2 datasheet) Smartpack S panel mount Smartpack 2
    Efficiency >96% (mains mode (AC/AC and AC/DC)), >94% (inverter mode (DC/AC))
    Operating temperature -40 to +55°C (-40 to +131°F), humidity 5 - 95% RH non-condensing
    Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
    Dimensions[WxDxH] / Weight 700 x 823x 1800mm (27,6 x 32,4 x 71”) / 250kg (551 lbs)
    Protection class IP 55
    Colour RAL 7035
    DESIGN STANDARDS
    Electrical safety EN 60950-1, EN 62040-1 UPS safety

    EMC ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15

    EN 61000-6-1 /-2/-3/-4

    Environment ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2) RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant

    1) AC load has priority. Maximum available DC output power and current is dependent on 3) If DC voltage is pulled below 43V the input current may increase above this level instant AC load and AC input voltage; i.e maximum 10,9 kW/18,9 kW at full AC power and

    nominal input for 230VAC.

    2) 40 - 45 VDC: reduced performance - no power boost and increased voltage THD on AC

    output

     

    * The Outdoor Rectiverter Cabinet with AC &DC feed in one cabinet ( Eltek Type 3 cabinet with different PowerCore)

     

    4、Product Display

Railway Station 21KW 48Vdc BTS Outdoor Telecom Cabinets OEM ODM

◆ Type:Outdoor Rectiverter Cabinet
◆ Product Name:Outdoor Cabinet
◆ Size:Type3 (1.5m/2m /2.2m )
◆ Cooling System:Aircon Or Heat Exchanger
◆ Structure:Steel Structure
◆ Ip Rating:IP65 Outdoor Cabinet
◆ External Size:Customized
◆ Application:Telecom, Railway Station, Base Station; Outdoor Cabinet For BTS
◆ Service:OEM Or ODM
◆ Warranty:3 Years
◆ Surface Finish:Painting
◆Open Side:Front Operation
◆High Light:21KW 48Vdc Outdoor Telecom Cabinets, 48Vdc BTS Outdoor cabinet, BTS Outdoor cabinet OEM ODM
Inquiry

PRODUCTS