1、Basic Infomation
◆ Place of Origin: CN
◆ Brand Name: Eltek
◆ Certification: CE
◆ Model Number: 241120.200
2、Payment & Shipping Terms
◆ Packaging Details: cartons
◆ Delivery Time: 8-10 weeks
◆ Payment Terms: L/C, T/T
◆ Supply Ability: 3000 pieces per month
3、Product Description
Eltek Micropack Rectifier Module 24V/240W (part No.: 241120.200)
Micropack 24V/240W WOR
The Micropack system is convection cooled, designed for less power hungry applications, but still with system functionality options to match any requirements.
Use as stand alone or in a flexible off the shelf configurable system.Compact, full-featured DIN rail power modules
The Micropack power system extends your network one step further. With load ranges typically between 120W and 1000W, and in 12, 24 and 48V options, the system is perfect for a great variety of applications.
Key features
◆ Convection cooled – inaudible
◆ Accepts 85 – 300 Vac/Vdc input
◆ 12, 24-30, 48 Vdc output versions
◆ NiCad support for 12 and 24 Vdc
◆ Quick-trip pulse to help open load MCB
◆ Pot-meter voltage adjustment for standalone
◆ Module alarm relay contact for basic monitoring without controller
◆ Active current sharing
◆ Modular approach in DIN-rail mountable back planes
◆ Off-the-shelf delivery
Parameters :
Model 12V / 120W 24V / 240W 48V / 250W Part number 241120.300 241120.200 241120.100 INPUT DATA Voltage range 85 - 300 V AC/ DC 1) Voltage range (nominal) 130 - 275 V AC/ DC 185 - 275 V AC/ DC 1) Frequency 0 - 66 Hz 1) Maximum current, 230V input / overall (boost) 0.6 A / 2.0 A 1.2 A / 2.0 A 1.2 A / 1.9 A Maximum earth leakage current 2.0 mA (@ 250V AC/ 50Hz) Power Factor 0.97 (@ 70 - 100 % load) 0.98 (@ 55 - 100 % load) 0.98 (@ 50 - 100 % load) THD (@ 230 VAC) < 5 % (@ 80 - 100 % load) < 5 % (@ 50 - 100 % load) < 5 % (@ 50 - 100 % load) Protection Varistor for transient protection, fuse in both lines (2x 2.0 A), shutdown above 300 V AC/ DC OUTPUT DATA Default voltage 13.6 V DC 27.2 VDC 53.5 VDC Voltage range 10.7 - 18.0 V DC 21.5 - 36 VDC 43.5 - 57.6 V DC Voltage range without controller 10.7 - 15.0 V DC 21.5 - 30 VDC 43.5 - 57.6 V DC # Pb cell supported (1.8 - 2.4 V DC/ cell) 6 - 7 12 - 15 24 # NiCad cell supported (1.05 - 1.65 V DC/ cell) 10 - 11 2) 20 - 222) - Max power, nominal / 60s boost 120 W / 160 W 240 W / 315 W 250 W / - Max current, @12/ 24/ 48V DC / boost / QT 3) 10 A / 15 A / 55 A 10 A / 15 A / 55 A 5 A / - / - Current sharing ±5% of maximum current from 10 to 100% load Static voltage regulation ± 0.5% from 10% to 100% load and nominal input Dynamic voltage regulation ± 5 % < 10ms, load step 10% to 90% or opposite at nominal output voltage Hold-up time, default voltage and full power 20 ms, V OUT > 10.7 VDC 20 ms, VOUT > 21.5 VDC 20 ms, VOUT > 43 VDC Rippel and noise, 30 MHz b.w. / psophometric < 200 mV PP / 5 mV RMS < 200 mV PP / 5 mV RMS < 150 mV PP / 2 mV RMS Protection Overvoltage shutdown, short circuit proof, high temperature, hot plug -in inrush current limiting, fuse OTHER SPECIFICATIONS Efficiency @ nominal input/ output, peak/ range 89.5% / >88%, 50-100% load 93.0% / >92%, 50-100% load 93.6% / >93%, 50-100% load Isolation 3.0 kVAC – input and output, 1.5 kV AC – input earth, 0.5 kV DC – output earth Alarms: Red LED 'on Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure Warnings: Yellow LED 'on' Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage Normal (module running): Green LED 'on' Alarm output (isolated) NO (+positive terminal), COM (-negative terminal). 60 V / 100 mA max MTBF (Telcordia SR-332 Issue I method III (a)) >480 000h (@T AMBIENT= 25°C) >480 000h (@T AMBIENT= 25°C) >500 000h (@T AMBIENT= 25°C) Operating temperature (5 - 95% RH non-cond.) Output power de-rates above temp / to -40 to +70°C [ -40 — +158°F]
+55°C / 50W @ +70°C
-40 to +60°C [-40 to +142°F]
+45°C / 80W @ +60°C
-40 to +75°C [ -40 to +167°F]
+55°C / 140W @ +75°C
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing Dimensions[WxHxD] / Weight 39.0 x 88.5 x 149mm [1.54 x 3.48 x 5.87"] / 0.5 kg [1.1 lbs] DESIGN STANDARDS Electrical safety UL 60950 -1, EN 60950 -1, CSA 22.2 EMC ETSI EN 300 386 V.1.3.2
EN 61000-6-1 / -2 / -3 / -4 / -5 4)
Mains Harmonics EN 61000 -3-2 Environment ETSI EN 300 019: 2 -1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ETSI EN 300 132-2
2002/ 95/ EC (RoHS) & 2002/ 96/ EC (WEEE)
Marine compliance
(EMC class B with AC filter)
DnV Rules for Classification of Ships, High Speed & Light Craft and DnV Offshore Standards 1) DC support for 241120.200 with primary FW 404088.009 (from HW revision 1.2) and 241120.100 from HW revision 2
2) 11/ 22 cells with max boost voltage 1.636 V DC/ cell
3) Quick-Trip function, if V OUT = 5 VDC a 35 ms current pulse is generated to help trip fuse/ MCB on short circuited branch
4) Only 12V and 24V
4、Product Display
Eltek Micropack Rectifier Module 24V/240W Part No 241120.200
◆ Model Name : Micropack 24/240W
◆ Input AC Voltage : 85 - 300 VAC
◆ Output Power : 240W
◆ Output Voltage : 21,5 - 36 VDC
◆ BrandA : Eltek
◆ Effciency : 93%
◆ Input DC Voltage : 85 - 300 VDC
◆ Output Current : 10 ADC
◆ Output Max Voltage : 36VDC
◆ High Light : 24V/240W Rectifier Module 241120.2, Eltek Micropack Rectifier 24V/240W 241120.2, Rectifier Module 24V/240W 241120.2
Eltek Micropack 24V /240W