1、Basic Infomation
◆ Place of Origin: CN
◆ Brand Name: Eltek
◆ Certification: CE
◆ Model Number: 241122.205
2、Payment & Shipping Terms
◆ Packaging Details: cartons
◆ Delivery Time: 8-10 weeks
◆ Payment Terms: L/C, T/T
◆ Supply Ability: 3000 pieces per month
3、Product Description
Eltek Rectifier Module FlatpackS 24V 1000W Flatpack2 24/1000HE (part no.:241122.205)
Flatpack S 24V/1000W HE
Applications in these markets demand state of the art, reliable and safe DC power systems. Flatpack S delivers an industry leading power density in its segment, many safety functions, wide operating temperature range and superb reliability in its small 217mm deep housing.
Compact and reliable rectifier for rail and power utilities applications
Used in the 3U rack with Smartpack S controller, the Flatpack S rectifiers cover 2 to 8kW applications using a minimum of space, less than 18 liters, and low heat dissipation.
Key features
◆ Small
◆ Short
◆ Power dense, 26 W/inch3
◆ High efficiency
◆ OR-ing protection on output
◆ Hot pluggable
Parameters :
Model Flatpack S 24/1000 HE Part number 241122.205 INPUT DATA Voltage (nominal range) 185 VAC/DC - 305 VAC / 300VDC Voltage (operating range) 85 VAC/DC - 305 VAC / 300VDC Frequency (nominal / range) 45 - 66 Hz / DC Maximum current 5.9 ARMS Power Factor > 0.99 at 50% load or more Protection Fuse
Shutdown above 305 VAC / 300 VDC
OUTPUT DATA Voltage (default) 26.7 VDC Voltage (adjustable range) 21 - 29 VDC Max power, nominal input 1000 W Max power, @ 85 VAC/DC 440 W Max current 41.7 A (@VOUT < 24 VDC) Current sharing ±5% of maximum current from 10 to 100% load Static voltage regulation (10-100% load) ±0.5% Dynamic voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms Hold up time >20ms; output voltage > 21 VDC Ripple < 150 mVPP , 30 MHz bandwidth
ProtectionBlocking OR-ing Diode, Short circuit proof, Over voltage protection and High temperature protection OTHER SPECIFICATIONS Peak Efficiency 92.5 % Isolation 3.0 kVAC - input and output, 1.5 kVAC - input earth, 0.5 kVDC - output earth Alarms (Red LED) Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure Warnings (Yellow LED) Rectifier in power de-rate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage Normal (Green LED) Input and output ok Potential alarm relay (normally closed) Opens on alarms and mains outage MTBF (Telcordia SR-232 Iss.3 Meth. II Case L1) >1 975 044 (@ Tambient : 25 °C) Operating temperature (5 - 95% RH non-cond.) - 40 - 85°C [-40 - 185°F ] Max output power de-rates above temp / to 45°C [+113°F] / 400 W Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing Dimensions[WxHxD] / Weight 72 x 41.5 x 217mm (2.83 x 1.63 x 8.54”) / < 850 g (1.9 lbs) DESIGN STANDARDS
Electrical safetyEN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013 IEC 60950-1:2013, UL 60950-1:2014
EMCEN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2011, -6-4:2007 + A1:2011, TS
61000-6-5, EN 300 386:v1.6.1, FCC CFR 47 Part 15:2013
Marine DNVGL-CG-03391), ABS PDA Certificate1)
EnvironmentETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
1) only valid for part number 241122.205M 4、Product Display
Eltek Rectifier Module FlatpackS 24V 1000W Flatpack2 24/1000HE (part no.:241122.205)
◆ Model Name : Flatpack S 24/1000HE
◆ Input AC Voltage : 80 - 300 VDC
◆ Output Power : 21,5 - 28 VDC
◆ Weight : 2 Kg
◆ BrandA : Eltek
◆ Effciency : 92.5%
◆ Input DC Voltage : 85 - 300 VDC
◆ Output Current : 41,7 ADC
◆ High Light : 92.5% Rectifier Module 241122.205, 92.5% Flatpack2 24/1000HE 241122.205, 92.5% Rectifier Module 24/1000HE 241122.205
FLATPACK 5 24/1000HE