1、Specifications
◆ Brand: Eltek
◆ Part No.: CTO31240.nnnn
◆ Protection Level: IP65
◆ Type: 36KW Outdoor Cabinet
◆ Rectifeirs: FP2 Rectifeirs 2000W /3000W
◆ Product Name: Telecom Outdoor Cabinet
◆ Application: Telecom, Railway Station, Base Station; Outdoor Cabinet For BTS
◆ Size: Type Enclousre
◆ Service: OEM Or ODM
◆ Cooling System: Aircon Or Heat Exchanger
◆ Warranty: 3 Years
◆ Input Voltage Max: 264Vac
◆ DC Intput Voltgae: 57,6 VDC
◆ Dimension: 705 X 2068 X 831 Mm
◆ Weight: 168 Kg
◆ High Light: Outdoor Telecom Cabinets 48Vdc 700A, Eltek 36KW street cabinets telecoms, street cabinets telecoms 48Vdc 700A
2、Basic Infomation
◆ Place of Origin: CN
◆ Brand Name: Eltek
◆ Certification: CE.UL
◆ Model Number: CTO31240.nnnn
3、Payment & Shipping Terms
◆ Delivery Time: 8-10 weeks
◆ Payment Terms: L/C, T/T
◆ Supply Ability: 400 sets /month
4、Product Description
Eltek Flatpack2 36KW outdoor cabinet with Type 4 Enclosure -48Vdc 700A cabinet for telecom (CTO31240.nnnn)
Flatpack2 Outdoor power system
The combination of cost-effective design, power density and reliability makes the Flatpack2 a product family that truly stands out and provides unparalleled network availability and power output.Together with our Type 4 enclosure platform it is designed for variety of applications and can be tailored to fit specific need with protection class of IP55.
Key features
l Complete outdoor system
l Smartpack R controller
l Advanced control and monitoring through ethernet port
l Super High Efficiency rectifiers
l Hot pluggable modules
l 8x battery breaker positions
l LVBD
l 16x load MCB positions
l LVLD (optional)
l IP55
Parameters :
MODEL 36KW Part number
(Configured Telecom power system)
CTO31240.nnnn POWER MODULE Rectifier 1) Flatpack2 48/3000 SHE INPUT DATA Voltage (range) / Frequency 85-264 VAC / 45-66 Hz AC Mains input configuration 3p400 VAC TN Surge protection SPD Class 2 Connection Terminal blocks, 35 mm2 max OUTPUT DATA Voltage -48 VDC Load current (maximum) 700 A BATTERY DISTRIBUTION Number of battery breaker positions 8x 100 A / 4x 125 A / 4x 200 A / 4x 250 A LVBD 800 A LOAD DISTRIBUTION Number of load MCBs positions 16x 18 mm (4x 18 mm + 8x 27 mm) LVLD (Optional) 150 A / 300 A / 500 A / 600 A Load breaker type DIN rail mounted, 18 mm and 27 mm wide CONTROL AND MONITORING Control and Monitoring unit 2) Smartpack R Inputs 6x Digital inputs (for monitoring of external equipment) Outputs 6x Alarm relays ENCLOSURE Enclosure type 3) Outdoor Type 4 Thermal Management system Fan and Filter: Dual fan configuration Finish Outdoor Polyester coating, Light grey RAL 7035 Ingress protection class IP55 OTHER SPECIFICATIONS Operating temperature -40 to +45°C [-40 to +113 °F] Storage temperature -40 to +85 °C [-40 to +185 °F] Dimensions (W x D x H) 705 x 831 x 2068 mm [27.8 x 32.7 x 81.4 inch] Weight (excluding modules) Approximately 168 kg [370 lbs] Cable entry Bottom entry 2x FL-21 cut-outs, with various cable entry glands Battery trays Optional battery tray(s) capable of holding a set of batteries up to 280kg Other general options Door switch, Heaters, Filter presence & Clogged filter detection, Document folder, Smoke detector, AC service socket, Service light, PC shelf DESIGN STANDARDS Electrical safety IEC/EN 62368-1 EMC ETSI EN 300 386 v2.1.1:2016
EN 61000-6-2 /-4
Environment ETSI EN 300 019-2-1 (Class 1.2) /-2 (Class 2.3) /-3 (Class 4.1E)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
1) See Flatpack2 rectifier datasheet for details
2) See Smartpack R controller datasheet for details
3) See Outdoor Type 4 datasheet for details 5、Product Display
IP65 Eltek 36KW Street Outdoor Telecom Cabinets 48Vdc 700A
◆ Brand: Eltek
◆ Protection Level: IP65
◆ Rectifeirs: FP2 Rectifeirs 2000W /3000W